Eaton Bussmann Inc. FRS-R-40
Bussmann Fusetron™ FRS-R-40 Current Limiting Time Delay Renewable Fuse, 40 A, 600 VAC/250 VDC, 200/20 kAIC Interrupt, RK5 Class, Cylindrical Body
Class RK5 Fuses
13694
FRS-R-40
Eaton Bussmann Inc.
$0.00
/ ea
- Amperage Rating: 40
- Body Size: 1.06 in Dia x 5.5 in L
- Body Type: Cylindrical
- Class: RK5
- Element: Dual
- Indicating/Non-Indicating: Non-Indicating
- Interrupt Rating: 200/20
- Material: Fiberglass
- Mounting Type: Holder
- Rejection/Non-Rejection: Rejection
- Response Time: 10 s at 500%
- Series: FRS-R
- terminal type: Ferrule End
- Type: Current Limiting Time Delay
- Voltage Rating: 600 VAC/250 VDC
Eaton Bussmann series FRS-R fuse, 40 A, Dual, Class RK5, Non-indicating, Ferrule end x ferrule end, 10 sec at 500%, 200 kAIC at 600 V,20 kAIC at 250 Vdc, Standard, 600 V, 250 Vdc
- Features
- Dual element feature provides the best time delay performance, allowing closer sizing and superior protection of motors and transformers
- Closer sizing allows for smaller fuses and less costly switches
- Class RK5 fuses with a 200 kA interrupt rating for use in a broad range of applications
- Provides motor overload, ground fault and short circuit protection
- Helps protect motors against burnout from overloads and 1 ph when sized properly
- Dual element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high performance short circuit and overload protection
- Offers a 10 s time delay at 5 times the rated current
- The time delay feature makes it possible to use fuse amp ratings which are much smaller than those of non-time delay fuses
- Considerable cost savings occur by permitting the use of smaller size switches, panels and fuses themselves
- Provides current limitation to help protect downstream components from high fault currents
- Gives motor running back-up protection to motors without extra costs