Eaton Bussmann Inc. FRS-R-250
Bussmann Fusetron™ FRS-R-250 Current Limiting Renewable Time Delay Fuse, 250 A, 600 VAC/300 VDC, 20/200 kA Interrupt, RK5 Class, Cartridge Body
Class RK5 Fuses
13709
FRS-R-250
Eaton Bussmann Inc.
$0.00
/ ea
- Amperage Rating: 250
- Body Size: 2.34 in Dia x 11.63 in L
- Body Type: Cartridge
- Class: RK5
- Element: Dual
- Indicating/Non-Indicating: Non-Indicating
- Interrupt Rating: 20/200
- Material: Fiberglass
- Mounting Type: Holder
- Rejection/Non-Rejection: Rejection
- Response Time: 10 s at 500%
- Series: FRS-R
- terminal type: Blade
- Type: Current Limiting Renewable
- Voltage Rating: 600 VAC/300 VDC
Eaton Bussmann series FRS-R fuse, 250 A, Dual, Class RK5, Non-indicating, Blade end x blade end, 10 sec at 500%, 200 kAIC at 600 V,20 kAIC at 300 Vdc, Standard, 600 V, 300 Vdc
- Features
- Provides motor overload, ground fault and short circuit protection
- When used in circuits subject to surge currents such as those caused by motors, transformers and other inductive components, these fuses can be sized close to full-load amps to give maximum over current protection
- The time delay feature makes it possible to use fuse amperage ratings which are much smaller than those of non-time delay fuses
- Considerable cost savings occur by permitting the use of smaller size switches, panels and fuses themselves
- Provides a good deg of short circuit protection (greater current limitation) to help protect downstream components from high fault currents
- Gives motor running back-up protection to motors without extra cost
- Helps protect motors against burnout from overloads and single phasing when sized properly
- Simplifies and improves blackout prevention (selective co-ordination ratios)
- Dual element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high performance short circuit and overload protection