Littelfuse SE-135-00

Littelfuse SE-135-00 Ground Fault Ground Check Monitor, 120/240 VAC, Isolated NO (1 Form A), NC (1 Form B), NO-NC (2 Form C) Output Contact, Surface/Panel Mount
IEC Electronic Protective Devices
7713700 SE-135-00
Littelfuse
$0.00 / ea

  • Dimensions: 8.4 in H x 3.9 in W x 5.2 in D
  • Mounting Type: Surface/Panel
  • Series: SE-135
  • Specifications: Isolated NO (1 Form A), NC (1 Form B), NO-NC (2 Form C) Output Contact
  • Voltage Rating: 120/240
The SE-134C/SE-135 is a microprocessor-based, combination ground-wire monitor and ground-fault relay for resistance grounded or solidly grounded systems. It continuously monitors the integrity of the ground conductor to protect portable equipment from hazardous voltages caused by ground faults. The SE-134C/SE-135 is field proven in monitoring trailing cables on large mobile equipment such as drag-lines, mining shovels, shore-to-ship power cables, dock-side cranes, stacker-reclaimers, submersible pumps, and portable conveyors.
  • Features
  • High quality
  • Adjustable pickup 0.5 to 12.5 A unit can be used on a wide variety of trailing cable applications
  • Adjustable time delay (1 to 2.5 s) -adjustable trip delay for quick protection and system coordination
  • Output contacts separate annunciation of ground fault and ground check faults
  • Indication of open or short ground check wire makes it easier to find faults
  • CT-loop monitoring - alarms when CT is not connected
  • High induced AC rejection makes unit suitable for applications with high voltages and long cables
  • DFT (harmonic) filter prevents false operation
  • Zener characteristic termination assembly provides reliable ground check loop verification
  • Fail safe circuits ensures ground check and ground fault circuits remain safe even in the event of equipment failure
  • Additional coating protects circuit boards against harsh environment